Features
Protection and control panel for one single-phase or three-phase pump, with overload and underload adjustment. Control with level probes, without probes (by underload) or with a flow detector. Suitable for wells, boreholes and pressure sets.
PROTECTIONS
- Circuit breaker against short circuits
- Thermal protection against overload, underload, phase failure and overvoltage
- Several lack-of-water detection modes
- Automatic or manual reset after a lack-of-water alarm
FEATURES
- 230 V or 400 V AC supply depending on model, 50/60 Hz
- Adjustable motor current from 1 to 18 A (up to 2.2 kW single-phase or 7.5 kW three-phase)
- Level control with two probes, one timed probe, without probes or with a flow detector
- Remote control input via dry contact or 6 to 24 V AC/DC
- Digital display with ammeter function and extra-low-voltage control circuit
- Compatible with the PumpCheck data reader
- IP65 protection · 240 x 190 x 110 mm · operating temperature from -10 to 55 °C